Video: How do you set up reference switching on the ATV212 drives?
Issue:
Reference switching between VIA and VIB
Product Line:
ATV21 and ATV212
Environment:
All
Cause:
Switching between two analog references VIA and VIB.
Resolution:
Reference switching can be accomplished by programming a logic input R (F112) or RES (F113) to 38.
Program your FNOD as your 1st reference and F207 as your 2nd reference.
Reference switching between VIA and VIB
Product Line:
ATV21 and ATV212
Environment:
All
Cause:
Switching between two analog references VIA and VIB.
Resolution:
Reference switching can be accomplished by programming a logic input R (F112) or RES (F113) to 38.
Program your FNOD as your 1st reference and F207 as your 2nd reference.
Publikováno pro: Schneider Electric Česká republika

