Jak vám dnes můžeme pomoci?
When creating a located variable of data type REAL in an M340 or M580 application, is there an addressing restriction?
Issue:
When creating a located variable of data type REAL in an M340 or M580 application, is there an addressing restriction?
Product Line:
M340, M580, Control Expert, Unity Pro
Resolution:
Yes. When programming an M340 or M580 application with Unity Pro, the located REAL variables must be assigned EVEN starting addresses such as %MW2 .%MW4, %MW50 . Addresses using
odd numbers such as %MW1, %MW3 or %MW49 would not be acceptable. Any 32 bit data type would have to follow this regimen. (DINT,DWORD,etc)
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: