Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
How do I read or write a program to/from the SY/MAX model 50 controller to the 8005PR4 hand held programmer?

Issue

How do you I read or write a program to/from SY/MAX model 50 controller to the 8005PR4 hand held programmer?

Product Line

SY/MAX

Environment

80005PR4

Resolution

To read a program from the SY/MAX model 50 controller to the 8005PR4 enter the following sequence:

  1. TRS, READ.
  2. Once "TRS P T L GO?" is displayed make sure the CPU is halted and a memory pack is installed and then press the ENTR key. "TRS P T L" is displayed during execution.
  3. When completed "TRS P T L END" is displayed.


To write a program from the 8005PR4 to the SY/MAX model 50 controller enter the following sequence:

  1. TRS, ENTR.
  2. Once "TRS L T P GO?" is displayed make sure the CPU is halted and either a 8005MP1 or 8005MP4 CMOS RAM memory pack is installed and then press the ENTR key. "TRS L T P" is displayed during execution.
  3. When completed "TRS L T P END" is displayed.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie