What is the function of the Reset button on the Modicon M340 platform power supply modules ?
Issue:
What is the function of the Reset button on the Modicon M340 platform power supply modules ?
Product Line:
Modicon M340
Resolution:
The Reset button of the M340 power supply modules, when pressed, simulates a power outage and launches a cold start of the application. In addition, all modules in the rack are power cycled, the alarm relay is forced open, and the OK LED is turned off.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.