Issue
How do I download to removable media (SD Card, Compact Flash Card or USB Memory Stick) using Vijeo Designer?
Product Line
Vijeo Designer, Harmony/Magelis HMI
Environment
Configuration software on Windows PC and physical HMI
Resolution
To download to removable media (SD Card, Compact Flash Card, or USB Memory Stick) using Vijeo Designer for the purposes of downloading to a Harmony/Magelis HMI later, follow these steps:
- Insert the removable media into your PC (a card reader may be required).
- Format the removable media in FAT32 format in Windows.
- Open your project in Vijeo Designer.
- In the Navigator pane, click on the name of the HMI ("Target1" by default).
- In the General Tab, next to Download choose File System.
- Set the IP for the Target HMI (where applicable).
- Initiate a Download as you would normally (right-click on the name of the HMI, and select "Download to (File System)…"
- Once the above completes, you can see the files required for download to the HMI in Windows Explorer.
- Eject the removable media from the PC.
- Transport the removable media.
- Plug it into the HMI (a power cycle may be necessary for SD and CF Cards).
- The HMI will show a prompt to ask if you wish to download the project to the HMI. Follow the instructions on the screen from this point.
Please review this video and the HTML help screenshots that follow:
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.