What is the effect of selecting the M340 PLC configuration parameter 'Initialize %MWi reset on cold start' ?
Issue:
What is the effect of selecting the M340 PLC configuration parameter 'Initialize %MWi reset on cold start' ?
Product Line:
Modicon M340 PLC
Resolution:
Cold Start = going from Unconfigured to Configured.
If you Transfer a project to an M340 that has a configuration with State Ram, Scenario 2 will leave existing state ram data unchanged.
If you power up an M340 with no SD card and then insert the SD card, Scenario 2 leave all data at 0.
- When checked, those %MW 's with initial values will be loaded. Any %MW not having an initial value will be cleared (initialized) to 0.
- If unchecked the all %MW's are cleared to 0 regardless of the presence of initial values.
- Unlocated variable values are maintained regardless of whether this box is checked or unchecked.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.