Jak vám dnes můžeme pomoci?
Report Manager error: The attempt to connect to the report server failed. Check your connection information and that the report server is a compatible version.
Issue:
When accessing http://localhost/Reports_ION, the Report Manager opens but displays the following error:
The attempt to connect to the report server failed. Check your connection information and that the report server is a compatible version.
Product Line:
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
SQL Server Reporting Services (SSRS)
Environment:
Report Manager (Reports_ION)
SQL Server Reporting Services configuration
RSWebApplication.config
Cause:
The Report Manager is not configured with a fully qualified Report Server URL. Instead, it references only a virtual directory, which prevents Report Manager from establishing a connection to the report server.Resolution:
- Navigate to the RSWebApplication.config file. By default, it is located at:
C:\Program Files\Microsoft SQL Server\MSSQL.2\Reporting Services\ReportManager\RSWebApplication.config
(The MSSQL.x folder number may vary depending on the SQL instance.) - Open RSWebApplication.config for editing (run the editor as Administrator).
- Locate the ReportServer configuration entries under the
<UI>section. - Update the configuration as follows:
- Set the ReportServerUrl value to the full URL, typically:
http://localhost/ReportServer_ION - Remove any value from ReportServerVirtualDirectory, leaving it empty.
- Set the ReportServerUrl value to the full URL, typically:
- After the changes, the configuration should appear similar to the following:
6. Save the file.
7. Recycle the Application Pool used by Report Manager in IIS Manager.
a. Recycling the Application Pool forces IIS to reload the updated configuration.
8. Refresh http://localhost/Reports_ION and confirm the Report Manager loads without error.
Recommendation:
If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.