Cyber Sciences SER-3200 (Sequence of Events Recorder Event Type "Test Status Change".

Issue
“Test Status Change” events appear in the SER‑3200 Event Log and users need to understand their cause and behavior.

Product Line
Cyber Sciences SER‑3200
Note: This behavior is specific to SER‑3200 test mode operation and is not related to PME version compatibility.

Environment
SER‑3200 Web Interface
Event Log
Test Mode / Simulator

Cause
The “Test Status Change” events are generated by the SER‑3200 simulator when the device is placed in test mode. Test mode automatically sequences inputs from off‑to‑on and back to off in 1 ms intervals. Each change in input state is recorded as an event, including the start and end of the test mode.

Resolution
Review the SER‑3200 Event Log to confirm that “Test Status Change” events originate from the internal simulator during test mode.


.Cyber Sciences Recorder

The test event records can be used to verify correct functionality with SCADA and power monitoring applications.

If input points are configured to trigger paging or email notifications, test mode will generate a large volume of alerts. To avoid excessive notifications, place the SER‑3200 into maintenance mode within ENM before running tests.

An attached file, “SER‑3200 Reference Guide (IB‑SER‑02)”, provides additional technical information. This guide includes details on Modbus register maps, communication protocol integration, time synchronization (PTP/NTP), web interface configuration, and access to high‑speed event logs. Refer to the full document for deeper integration and configuration guidance.

Schneider Electric Česká republika

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.