Goals and Symptoms
Summary
Event Timestamps in Management Console are displayed in Coordinated Universal Time (UTC) rather than in local time. Adjusting the server time zone in Windows settings has no effect on the timestamps.
Symptoms
Management Console Events are in UTC instead of local time, regardless of server time zone settings.
Facts and Changes
Keywords
Event
Management Console
Time
Timestamp
Greenwich Mean Time
UTC
Causes and Fixes
Resolution
A timestamp setting in Management Console is not configured correctly.
- Open the Event tab under Devices or Sites, whichever is showing UTC time.
- Right-click the grey section in the title bar and select Properties.
- Select the Row Properties tab from the Option window.
- Check the Convert timestamps to local date and time box.
All timestamps will now be displayed in the local time zone of the computer running Management Console.
NOTE: This setting is applied to all Event timestamps.
Original article#16518
Last Revised: October 31, 2007
Public
All content © 1992-2007 Schneider Electric
Legacy KB System (APS) Data: RESL189224 V1.0, Originally authored by KBAdPM on 11/16/2007, Last Edited by KBAdPM on 11/16/2007
Related ranges: ION Enterprise V5.6, ION Enterprise V5.5, ION Enterprise V5.0
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.