Energy Pulsing cannot be setup on the E5600 via the Optical Probe
Issue:
When connecting to an E5600 meter for the first time, energy pulsing cannot be properly enabled when configuring the meter through the optical port only.
Product Line:
E5600 meter
Environment:
ION Setup
Optical probe
Modbus communication
Cause:
Although KY Relay #1 and KY Relay #2 can be enabled and KT/KE values configured through the optical port, the meter will not generate pulses until meter pulsing is explicitly enabled via the Modbus interface.
When connected through Modbus, the same configuration screen indicates that the meter is ready to pulse through its digital output, but the internal pulsing enable flag is not set by optical configuration alone.
Resolution:
If meter pulsing is configured via the optical probe and no pulses are observed at the digital output, complete the following steps:
- Communicate to the meter using Modbus (for example, via ION Setup).
- Navigate to the KY Relay configuration.
- Enable KY Relay #1 and KY Relay #2, then click Send to apply the settings.
- Confirm that a valid KE value is selected.
- Verify that the digital output now generates pulses.
After pulsing has been enabled through Modbus, the meter will correctly generate energy pulses on the configured digital output.
Note: E5600 Meter is obsolete and the end of commercialization was 2015, click the following link for more information: E5600 Meter Obsolescence (obsolete) End of Commercialization
Publikováno pro: Schneider Electric Česká republika


Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.