How to connect Unity Pro to a Modbus PLC through a TSXETG100 Ethernet gateway
Issue
How can Unity Pro connect to a Modbus PLC through a TSXETG100 Ethernet gateway?
Product Line
- TSXETG100
- Unity Pro
Environment
The TSXETG100 is used as the communication gateway between Unity Pro and the PLC.
Resolution
-
Configure the PLC Modbus address in the TSXETG100
- Open the TSXETG100 web interface by entering its IP address in a web browser.
-
-
- Log in to the TSXETG100.
- Select Setup > Device List.
-
-
-
- Add the Modbus address of the PLC to the device list.
- Select Apply to save the configuration.
-
-
Configure the PLC address in Unity Pro
- Open the Unity Pro project.
- Select PLC > Set Address.
- In Media, select TCPIP.
- In the Address field, enter the TSXETG100 IP address followed by a semicolon (
;) and the PLC Modbus address.
In this example:
192.168.40.2is the TSXETG100 IP address.1is the Modbus address of the PLC.
-
Connect to the PLC
- Confirm the address configuration.
- Select PLC > Connect.