Reporter Warning: "No Mail System Installed"
Goals and Symptoms
Summary
Reporter failed to send result via email to recipients in the distribution list. When the report is generated, the report status showing warning message: "No Mail System Installed". This article explains the steps to diagnostic and narrow the cause of the problem.
Symptoms
Most important text from above screenshot:
==================
Report Status
-----------------
Initializing report generator
Starting report: ....
alper: Querying <ion.ETH7600>Data Rec 15
alper: Validating records
*WARNING* alper: Adding leading missing records
*WARNING* alper: CANCELING validation due to unexpected rec... <message cut off in screenshot>
Saving report as: c:\...
*WARNING* Recipients not emailed - no mail system installed
Finished report: dememe
Click the Close button to view the report.
===================
Facts and Changes
Keywords
ION Reporter
RepGen
Mail System
Causes and Fixes
Cause
Reporter uses Excel to send a copy of the report via email. This only works on a MAPI-enabled system.
To narrow down the problem, try the following 3 things:
1. Ensure that Excel can send email.
a) Launch Excel, and go to File > Send To > Mail Recipient (As Attachment). A new email should be created with the .xls as an attachment.
b) Send this email to the desired email address.
c) If cannot successfully perform the above, check that all mail settings are correct in Outlook.
2. Run the attached 'Mail System Test.xls' Excel macro and report the results.
a) Go to Tools > Macro > Security > Medium.
b) Reopen this file and select Enable Macro.
c) Go to Tools > Macro > Macros... and select 'MailerCK, and click Run.
3. Obtain the report template file and test whether or not it works on your machine. You can find the report template file in the following directory:
x:\Program Files\Power Measurement\ION Enterprise\config\reports
Resolution
More Information
The following is the code for the Mail System Test.xls macro:
-
- Sub MailerCK()
'This checks what mailer is installed on your system.
Select Case Application.MailSystem
Case xlMAPI
MsgBox "Mail system is: Microsoft Mail."
Case xlPowerTalk
MsgBox "Mail system is: PowerTalk."
Case xlNoMailSystem
MsgBox "No mail system installed!"
End Select
End Sub
- Sub MailerCK()
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.