How can you program the R1 or R2 relays on the ATV31 or ATV312 drives?

Issue:
Programming the R1 or R2 on the ATV31/ATV312 drives.

Product Line:
ATV31 or ATV312

Environment:
All

Cause:
Setting up R1 and R2 relays on the ATV31 or ATV312 drives?

Resolution:
Note: "press Enter" means press in on the dial, and "scroll down" means turn the dial clockwise.

  1. While at RDY on the drive's display, press Enter
  2. Scroll down to I/O menu and press Enter
  3. Scroll down to R1, press enter, and choose your desired setting. Example: FLT is drive fault.
  4. Scroll down to R2 enter and choose your desired setting. Example: RUN is drive running.


For further detail, please refer to page 50 in the ATV312 Programming Manual.
https://www.schneider-electric.com/en/download/document/BBV46385/