Why might an ATV212 Drive always run at the low speed setting and not follow the analog input signal?

Issue:
ATV212 running at low speed and not following the analog input signal

Product Line:
Altivar ATV212

Environment:
All

Cause:
Drive is not following the remote analog signal coming in on VIA or VIB

Resolution:
The low speed setting is parameter LL.

Verify that the VFD is setup to look for the analog input:
DIP switch SW100 position VIA at U (voltage) or I (current), VIB at U (voltage)
Frequency mode select, FMOd:
1 = VIA input
2 = VIB input

Verify the analog input signal by measuring the mA or Vdc on VIA / VIB.  Also check polarity, (+) on VIA / VIB and (- ) on CC.

Logic input R has factory default assignment as preset speed, F112 = 6, Sr1 = 15Hz.  If R is active, the VFD will run at 15Hz or LL (low limit) only. Check / correct the R input status and assignment.  Note that in an S-Flex product, R is a run permissive input, F112 = 1.  If a replacement ATV212 is installed or the VFD was reset to factory defaults, reprogram the VFD per the S-Flex manual.

Verify that the PID parameter, F360, is set correctly:
0 = no PID control
1 = PID per VIA feedback
2 = PID per VIB feedback

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie