How to reset the password of the FlexNet Publisher back to default

Issue
The FlexNet Publisher (FNP) is a web interface hosted on the PME server for configuring licensing components.

The URL is https://schneider-electric.flexnetoperations.com/

The default username and password for FlexNet Publisher (FNP) is admin/admin.

If the password is changed to something else, the default admin/admin combination will not work.

Product Line
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
NOTE: Does NOT apply to PME 9.0 and greater

Environment
FlexNet Publisher

Cause
The default password has been changed (admin is the default password).

Resolution

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

Following the procedure below, the password of the FlexNet Publisher can be reset to its default: "admin" (without the quotation mark).

  1. Navigate to:
    On Power Monitoring Expert 7.2.x:
    C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Floating License Manager\FLEXnet Publisher License Server Manager\conf

    On Power Monitoring Expert 8.x
    C:\ProgramData\Schneider Electric\Floating License Manager\FLEXnet Publisher License Server Manager\conf
  2. Open the 'server.xml' in Notepad or any suitable XML editor.
  3. Search for: lastName="Administrator"
  4. Replace the contents of the password field as shown below:
    id="admin" lastName="Administrator" password="(ENC-01)AxlKxBaCLbp4iPFsjJ6eOFtE+qoJWH8ThHIKN9DgdEgILS9j" passwordExpired="false"

    For example if you want to change the password back to admin, here is what the line would look like:
    id="admin" lastName="Administrator" password="admin" passwordExpired="false"
  5. Restart the "lmadminSchneider" service from 'Services'.
  6. Login to the Flexnet Publisher by navigating to https://schneider-electric.flexnetoperations.com/ and clicking on 'Administration'. Use the following credentials to sign in if the password was changed to "admin" on step 4:
    Username: admin
    password: admin

    Note: The username is always "admin."

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie