How to Configure SQL Server Agent to Restart Services Automatically

Xssue
SQL Server and SQL Server Agent services automatically stop unexpectedly.

Product
Struxureware Power Monitoring 7.0.x

Power  Monitoring Expert 7.2.x

Power  Monitoring Expert 8.x

Power  Monitoring Expert 9.x

ION Enterprise

ION EEM

Environment
SQL Server 2005

SQL Server 2008 R2

SQL Server 2012

SQL Server 2014

Cause
Troubleshooting possible system issues.

Resolution
You can configure SQL Server Agent to restart the SQL Server and SQL Server Agent services automatically if they stop unexpectedly.
Configuring automatic restart of these services is a best practice because it may prevent a prolonged system outage if the server is
unmonitored and these services stop for some reason.

To configure automatic service restart :

1) Open the SQL Server Management Studio Management folder, right-click the SQL Server Agent entry, and select Properties.
2) On the General page, select the Auto Restart SQL Server If It Stops Unexpectedly check box.
3) Also select the Auto Restart SQL Server Agent If It Stops Unexpectedly check box.
4) Click OK.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie