Issue:
ATV21 and ATV212 parameter that activates Catch on the Fly
Product Line:
ATV21 and ATV212 drives.
Environment:
All models, All serial numbers.
Cause:
Clarification of function and how to configure it is needed.
Resolution:
Parameter F301 is used to configure the Catch on the Fly function. It has 5 possible settings:
0 : Deactivated
1 : Activated after brief power loss
2: Activated after run permissive is restored
3: Activated after a brief power loss or when run permissive is restored.
4: Activated at every startup.
ATV21 and ATV212 parameter that activates Catch on the Fly
Product Line:
ATV21 and ATV212 drives.
Environment:
All models, All serial numbers.
Cause:
Clarification of function and how to configure it is needed.
Resolution:
Parameter F301 is used to configure the Catch on the Fly function. It has 5 possible settings:
0 : Deactivated
1 : Activated after brief power loss
2: Activated after run permissive is restored
3: Activated after a brief power loss or when run permissive is restored.
4: Activated at every startup.
Publikováno pro:Schneider Electric Česká republika

