Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
How do I install Vijeo Designer Application onto a New Magelis running Windows and Vijeo Designer Runtime from USB Stick

Article available in these languages: Španělština

Make sure you are using a quality USB stick
Vijeo Designer and the Vijeo Designer Runtime must be matching revisions
Format the USB stick - FAT32

In Vijeo Designer - Navigator - Select your target
with the Property Inspector - Select Download - Click the + to expand - Change Download to File System - Change Path to the Drive location of the USB stick

Right click your target - Select Download to (File System)...
[The Project must be saved in order to download a backup to the target. Save project and continue download] Select Yes
After Downloading Complete
Safely Remove USB Mass Storage Device
Remove USB Stick

Install USB Stick on Magelis
Select Start -> All Programs->Schneider Electric->Vijeo Designer->Tools->Vijeo Designer Application Installer
Browse for the .VDA file on the USB Stick
Open
After it is complete

Select Start ->all programs->Schneider Electrci->Vijeo Designer->Vijeo Designer Runtime

Your Application should start running.


Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie