While Importing xml file in the BMXNOR0200 firmware version V1.6 there is error saying import not successful ?
Issue: When user imports the XML, the error "Import not Successful appears"
Product Line: BMXNOR0200 V1.6
Environment: Unity Pro V12
Resolution:
The XML file contains the module and protocol configuration parameters. One can easily export these parameters into a XML file.
This file can later be restored into the module by importing it from the module webpage.
However if the module communication channel parameters are not defined, then you get an error import not successful while importing the xml file.

So its very important to define the communication channel parameter before exporting the configuration into the xml file.
Product Line: BMXNOR0200 V1.6
Environment: Unity Pro V12
Resolution:
The XML file contains the module and protocol configuration parameters. One can easily export these parameters into a XML file.
This file can later be restored into the module by importing it from the module webpage.
However if the module communication channel parameters are not defined, then you get an error import not successful while importing the xml file.
So its very important to define the communication channel parameter before exporting the configuration into the xml file.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.