How to identify and update outdated Statistics in SQL Server
Issue
A user may be experiencing performance issues when running SQL queries.
Product Line
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Environment
Power Monitoring Expert Software with either SQL Server Versions (2005- 2022)
Cause
Outdated statistics can make the SQL server choose a non-optimal execution plan causing undesirable slow response times for certain queries.
Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*
To identify tables within the database which have outdated statistics, the following query can be used.
SELECT OBJECT_NAME(id) AS Table_Name, st.[name] AS Tname, si.name,
STATS_DATE(id, indid) AS DateLastUpdate,rowmodctr rowsModifiedSinceLastUpdate
FROM sys.sysindexes AS si
INNER JOIN sys.[tables] AS st ON si.[id] = st.[object_id]
INNER JOIN sys.schemas AS ss ON st.[schema_id] = [ss].[schema_id]
WHERE STATS_DATE(id, indid)<=DATEADD(DAY,-1,GETDATE())
AND rowmodctr>10
ORDER BY[rowmodctr] DESC
Once you have identified tables with outdated statistics, the UPDATE STATISTICS statement can be used to
bring the statistics back up to date.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Produkt:
Zjistěte více
Produkt:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.