Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
How do I configure Vijeo Designer to play sound file on the HMI
Issue:
How to configure Vijeo Designer to play sound file on the HMI


Product Line:
Vijeo Designer


Resolution:
Using Sound methods, you can play sound files (.wav, .daf) on the target machine. You can play one sound file at a time.
Note: Not all target machines support the playing of sound files. Refer to your target machine manual to check if it supports sound files.

1. You will need to add the sound file under the target environment.
2. You can use the system sound method below to play the file.

Methods
Sound.play : Plays the sound file once.
Sound.loop : Repeats playing the sound file.
Sound.stop : Interrupts and stops playing any sound files.

If using scripting to play a file, the string format should be Sound.play( "AliasName" ); where "AliasName" is the alias name given in the sound file editor

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie