Do the TM3 analog input modules supply power to the inputs?

Issue:
Reading analog inputs on a TM3 module

Product line:
All TM3 analog input modules for all Products that can use the TM3 modules

Environment:
Exostruxure  Machine Expert, So Machine Expert Basic, ( formally SoMachine and SoMachine Basic).

Cause:
Not able to read any analog inputs on card.

Resolution:
No the TM3 analog input modules need to have a loop supply or a self powered field device to power the input.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.