What is the difference between Ref 1B switching and Ref 2 switching on the ATV61 and ATV71 drives?
Issue:
Difference between Ref 1B switching and Ref 2 switching on the ATV61/71 drives.
Product Line:
Altivar ATV61 and ATV71 drives
Environment:
All
Cause:
Customer needs to know why do we have two reference switching on the ATV61 and ATV71 drives?
Resolution:
Ref 1 B switching will allow you to switch between Ref 1 channel in Menu 1.6 and Ref 1 B channel in Menu 1.7.
Ref 2 switching will allow you to switch between Ref 1 channel in menu 1.6 and Ref 2 channel in menu 1.6
See the attached programming manual for programming assistance on setting them up.
Difference between Ref 1B switching and Ref 2 switching on the ATV61/71 drives.
Product Line:
Altivar ATV61 and ATV71 drives
Environment:
All
Cause:
Customer needs to know why do we have two reference switching on the ATV61 and ATV71 drives?
Resolution:
Ref 1 B switching will allow you to switch between Ref 1 channel in Menu 1.6 and Ref 1 B channel in Menu 1.7.
Ref 2 switching will allow you to switch between Ref 1 channel in menu 1.6 and Ref 2 channel in menu 1.6
See the attached programming manual for programming assistance on setting them up.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.