What are the meanings of the various status LED operations on an Enercept Meter?
Issue
A user would like to know the various reasons behind the status LED's on an Enercept Meter.
Product Line
Enercept Meters
Environment
Enercept meter troubleshooting
Cause
The Enercept meter has a status LED for diagnostic purposes. A user would like to know more information about the various states of the status LED for troubleshooting.
Resolution
A user would like to know the various reasons behind the status LED's on an Enercept Meter.
Product Line
Enercept Meters
Environment
Enercept meter troubleshooting
Cause
The Enercept meter has a status LED for diagnostic purposes. A user would like to know more information about the various states of the status LED for troubleshooting.
Resolution
| If the LED blinks green | The product is functioning normally. It blinks slow, approximately one second on, then one second off. |
| If the LED is red and blinking slowly | In most cases, incorrect wiring will cause the STATUS LED to blink RED (slowly). However, a power factor lower than 0.5 could cause the LED to blink this way, even if the unit is installed properly. |
| If the LED is red and blinking quickly | CT’s maximum current rating has been exceeded |
| If the LED does not blink | Check fuses and voltage connections. STATUS LED should blink regardless of CTs, Modbus connections, and DIP switch settings. |
| If the LED does not blink. | When the unit is wired on the load side of an adjustable frequency drive and the LED does not blink, the unit’s thermal fuse could be blown. The unit must not be installed on the load side of an adjustable frequency drive. |
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.