Where can I find the SCCR ratings for ATV61 or ATV71, 18 pulse enclosed drives ?

Issue:
Looking for the SCCR ratings for ATV61 or ATV71, 18 pulse drives ?

Product Line:
ATV61 / ATV71

Environment:

PowerGard 18 Pulse Drives

Cause:
None

Resolution:
PowerGard enclosed drive controllers have a short-circuit current rating of 100 kA @ 480 V (RMS symmetrical).

See Altivar® 61/71 PowerGard™ Class 8839 Type CPD 18-Pulse Adjustable Speed Drive Controllers Instruction Bulletin 30072-451-53 for details.

https://www.se.com/us/en/download/document/30072-451-53/