How is a fault code cleared or reset, on ATS22?
Issue:
Needs to clear a fault code, on the ATS22 soft start.
Product Line:
Altistart 22
Environment:
All models
Cause:
The fault code must be cleared to make ATS22 functional.
Resolution:
After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:
1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.
2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.
3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.
4) Use Modbus command word 752 and write a 1 to bit 3
Note that several fault codes require method 1) above. These are InF, trAP, SCF.
Needs to clear a fault code, on the ATS22 soft start.
Product Line:
Altistart 22
Environment:
All models
Cause:
The fault code must be cleared to make ATS22 functional.
Resolution:
After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:
1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.
2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.
3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.
4) Use Modbus command word 752 and write a 1 to bit 3
Note that several fault codes require method 1) above. These are InF, trAP, SCF.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.