I have set the variables to be retentive but how come the HMISTO does not retain the values on power cycle?

Issue:
I have set the variables to be retentive but how come the HMISTO does not retain the values on power cycle?

Product Line:
Magelis, HMISTO501, HMISTO511, HMISTO512

Resolution:
The HMISTO series only retains the value at every hr interval.  This is a hardware limitation and there is no work around for this.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.