Where can I find programming assistance to set up an ATV61/ATV71 drive with an VW3A3316 Ethernet IP card using assemblies 20 and 70?
Issue:
Set up an ATV61/ATV71 drive with a VW3A3316 Ethernet IP card using assemblies 20 and 70.
Product Line:
Altivar ATV61 and ATV71 with Ethernet VW3A3316 option card.
Environment:
All
Cause:
Needs to set up an ATV61 drive with an Ethernet IP card to use Assemblies 20 and 70.
Resolution:
PLC's Ethernet scanner module needs to be configured as follows
Assembly 20 2 words or 4 bytes (output table)
Assembly 70 2 words or 4 bytes (input table)
Configuration size 6
Single INT
Drives programming needs to be exactly like this there are no exceptions
Menu 1.6
Command menu
Reference 1 channel = Com card or NET
Profile= Separate control
Command switching= C312
Command channel 1= Com card or NET
Command channel 2= terminal control
Reference 2 switching= C313
Reference 2 channel= AI2 or AI1 (you choose)
Menu 1.7
Ref 1b switching = channel 1 active (applies only to the ATV61)
See the tables below for the assembly mapping for the Command word and for reading the ETA status.

Additional important information about setting the speed reference from the network.

Set up an ATV61/ATV71 drive with a VW3A3316 Ethernet IP card using assemblies 20 and 70.
Product Line:
Altivar ATV61 and ATV71 with Ethernet VW3A3316 option card.
Environment:
All
Cause:
Needs to set up an ATV61 drive with an Ethernet IP card to use Assemblies 20 and 70.
Resolution:
PLC's Ethernet scanner module needs to be configured as follows
Assembly 20 2 words or 4 bytes (output table)
Assembly 70 2 words or 4 bytes (input table)
Configuration size 6
Single INT
Drives programming needs to be exactly like this there are no exceptions
Menu 1.6
Command menu
Reference 1 channel = Com card or NET
Profile= Separate control
Command switching= C312
Command channel 1= Com card or NET
Command channel 2= terminal control
Reference 2 switching= C313
Reference 2 channel= AI2 or AI1 (you choose)
Menu 1.7
Ref 1b switching = channel 1 active (applies only to the ATV61)
See the tables below for the assembly mapping for the Command word and for reading the ETA status.
Additional important information about setting the speed reference from the network.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.