How do you program the ATV12 drive to do 2 wire start stop from the terminals and speed control from the local knob?
Issue:
Program the ATV12 drive to do 2 wire start stop from the terminals and speed control from the local knob.
Product Line:
Altivar ATV12
Environment:
All
Cause:
Needs to start stop the drive in terminal mode and use the knob for speed control.
Resolution:
Step 1
Put the drive in local mode by holding the MOD button for 4 seconds or until the display flashes LOC.
you will see 3 LEDs flashing or scrolling on and off
Step 2
Now hold the ESC button for 4 seconds or until the 3 LED stop scrolling and start to flash all 3 at once.
Step 3
Now you can program the drive with the knob or wheel. Push enter on the wheel, scroll down to CONF enter, scroll down to CTL menu enter,
FR1= A1U1 enter
CHCF= SEP enter
CD1= term enter
IO menu
tct= LEL
TCC= 2C
rrs= optional for reverse LI2
When you are done with all of your programming Hold the ESC button again for 4 seconds or until the 3 leds start to scroll again.
Now you are ready to run your drive by starting in terminal mode and using the knob as the speed control.
Program the ATV12 drive to do 2 wire start stop from the terminals and speed control from the local knob.
Product Line:
Altivar ATV12
Environment:
All
Cause:
Needs to start stop the drive in terminal mode and use the knob for speed control.
Resolution:
Step 1
Put the drive in local mode by holding the MOD button for 4 seconds or until the display flashes LOC.
you will see 3 LEDs flashing or scrolling on and off
Step 2
Now hold the ESC button for 4 seconds or until the 3 LED stop scrolling and start to flash all 3 at once.
Step 3
Now you can program the drive with the knob or wheel. Push enter on the wheel, scroll down to CONF enter, scroll down to CTL menu enter,
FR1= A1U1 enter
CHCF= SEP enter
CD1= term enter
IO menu
tct= LEL
TCC= 2C
rrs= optional for reverse LI2
When you are done with all of your programming Hold the ESC button again for 4 seconds or until the 3 leds start to scroll again.
Now you are ready to run your drive by starting in terminal mode and using the knob as the speed control.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.