What is the maximum distance for the TM3 (TM3XTRA1 / TM3XREC1) transmitter and receiver modules?
Issue
What is the maximum cable length between the Modicon TM3 transmitter (TM3XTRA1) and receiver (TM3XREC1) modules?
Product Line
Modicon TM3 Expansion I/O modules for M221, M241, M251, M262 PLCs
Environment
Physical PLC
Resolution
5m (16.4ft) is the maximum length between the TM3 transmitter (TM3XTRA1) and receiver (TM3XREC1) modules.
The part number of the recommended cable is VDIP184546050 (5.0 m).
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.