How do you program the ATS22 softstarter to trip if it exceeds some number of starts per hour?

Issue:
How can ATS22 be programmed for a fixed number of starts per hour?

Product Line:
Altistart ATS22

Cause:
Wants to delay the total number of times the softstarter can be started in one hour.


Resolution:
Programming:
Adj menu
Snb= number of starts  Off or 1 thru 10
SLG= Start period 1 min thru 60 mins

Example= if Snb= 3 and SLG is 10 mins   you can start and stop the drive 3 times in 10 mins.  If you exceed the programmed start time the drive will trip out on SnbF.

***

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Přílohy
ats22_user_manual_en_bbv51330_02.pdf [3.02 MB]
Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie