Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
Can a standalone StruxureWare Power Monitoring Expert 7.2.2 system be moved from a Standalone Server to a Distributed system?
Issue
Migrating from a PME 7.2.2 Standalone System to a PME 7.2.2 Distributed System

Product Line
Power Monitoring 7.2.2

Environment
Standalone System to Distributed System

Cause
It is sometimes desirable to migrate from standalone architecture to distributed system while keeping the data, configuration and setup intact.

Resolution

*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system. Always backup the registry before making any changes.*

*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

See the attached document for instructions on how to Migrate from a standalone to distributed system architecture.

Schneider Electric Česká republika

Přílohy
PME_7.2.2standalonetodistributed.pdf [151.7 KB]
Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie