Jak vám dnes můžeme pomoci?

What can cause an CFF fault on the ATV12 drives?

Issue:
CFF fault  on the ATV12 drives?

Product Line:
Altivar ATV12

Environment:
All

Cause:
Drive is powering up with an CFF fault and will not clear.

Resolution:
CFF= incorrect configuration fault.

Possible causes:
-HMI block replaced by and HMI block configuration on a drive with a different HP ratings.
-The current parameter of the customers parameter is inconsistent.

Remedy: Try resetting the drive back to a factory default by going into:
ConF  menu enter
FCS menu enter
change FCS menu to InI and hold for 2 seconds.
Now power cycle the drive.
If the fault clears, now try and reprogram the drive.  If you are still getting the CFF fault then you will need to replace the drive.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie