Jak vám dnes můžeme pomoci?

What is the replacement for the Magelis XBTG5330 HMI?

Issue:

What is the replacement for the Magelis XBTG5330 HMI?

Product Line:

Magelis XBTG5330 HMI

Resolution:

The Magelis XBTG5330 HMI was replaced by the XBTGT5330. However, the end of commercialization for the Magelis XBTGT5330 HMI was on June 30, 2015. The XBTGT5330 can be replaced by the HMIGTO5310.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie