Is there a way to correct a 'Win87em.dll' error in Concept programming software?
Issue:
Is there a way to correct a 'Win87em.dll' error in Concept programming software?
Product Line:
Concept
Resolution:
The win87em.dll error usually occurs in Concept when online animating a function block.
"Application error
Concept cause a General Protection Fault in module WIN87EM.DLL at 0001:02C9. Choose close.
CONCEPT will close."
This error can be corrected by doing the following:
1/ Copy hide87.com file into the windows\system32 folder.
2/ Open c:\windows\system32\autoexec.nt with Notepad
Create the autoexec.nt file if it does not exist.
3/ Insert the following at the top of the file:
lh %SystemRoot%\system32\HIDE87.com
4 Save changes to autoexec.nt and reboot the PC.
(The Windows 80×87 emulator library, WIN87EM.DLL, works at the 16-bit-Windows level to virtualize the coprocessor among multiple
Windows-based applications that run inside the system VM.) HIDE87 is supposed to hide the math coprocessor from the kernel.)
For this reason, if you encounter this when running Concept, you may want to install Concept on a VM where hiding the math coprocessor might not
have the same impact it would have on the host OS.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.