Cannot assign located variable to the Unity Momentum IO
Issue
Cannot assign located variable to the Unity Momentum IO
Product Line
Unity Momentum 171CBU*****
Environment
Unity, Control Expert
Resolution
Located variables cannot be assigned to the Momentum IO as in Concept.
Typically, the hardware configuration information is stored in %KW words for the Unity PLC's. Due to the hardware
limitation, the use of %KW words is not allowed for the Momentum PLC. As a result, Unity is forced to use reserved
%MW words for the module configuration information. The %MW words used for the configuration are intentionally
locked out to prevent the user from changing the values. This also locks out the the use of a %MW assignment for the IO.
Cannot assign located variable to the Unity Momentum IO
Product Line
Unity Momentum 171CBU*****
Environment
Unity, Control Expert
Resolution
Located variables cannot be assigned to the Momentum IO as in Concept.
Typically, the hardware configuration information is stored in %KW words for the Unity PLC's. Due to the hardware
limitation, the use of %KW words is not allowed for the Momentum PLC. As a result, Unity is forced to use reserved
%MW words for the module configuration information. The %MW words used for the configuration are intentionally
locked out to prevent the user from changing the values. This also locks out the the use of a %MW assignment for the IO.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.