Jak vám dnes můžeme pomoci?

Event Notification Module 8.3 Schneider Electric Event Gathering Service (SEEGS) Patch

Issue
When operating the Event Notification Module software version 8.3 as an OPC client with either Alarm Sentry or another OPC server, the "Schneider Electric Event Gathering Service" may increase memory usage until the service crashes and/or alarms stop coming into ENM.

Product Line
Event Notification Module (ENM) 8.3

Cause
There is an issue with the Schneider Electric Event Gathering Service that will cause it to continually increase memory usage when any OPC event sources are selected.

Resolution

  1. Place the system in Maintenance Mode within the ENM Configuration Utility to prevent redundant alarm emails on restart.
  2. Stop the Schneider Electric Event Gathering Service
  3. In the Event Gathering Service directory, replace the Module.OPCAlarmClient.dll with the attached file. (Note: Do not keep the old dll in the directory as it will cause an exception on startup.)
  4. Default Location: C:\Program Files (x86)\Schneider Electric\StruxureWare Solutions\Event Gathering Service
  5. Edit the SEEGS.exe config file located in this directory by adding the following entry in the appSettings section:

<add key="opcCheckInterval" value="30000"/>

image



6. Restart the Schneider Electric Event Gathering Service

7. Turn Maintenance Mode Off in the ENM Configuration Utility.


NOTE:
Please notify Brett Cussac at brett.cusaac@schneider-electric.com to notify of any deployments of this patch.

Schneider Electric Česká republika

Přílohy

Zjistěte více

Zjistěte více

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.