How do we control the Security InActivity timeout with a variable in Vijeo Designer?
Issue:
How do we control the Security InActivity timeout with a variable in Vijeo Designer?
Product Line:
Vijeo Designer (all versions)
Resolution:
Often times, the built-in time settings for the InActivity timeout for the Vijeo Designer Security feature are insufficient. Sometimes we would like a smaller amount of time to elapse instead, rather than the 1 minute minimum that is offered. In order to have a customizable Auto Logout Threshold, we can make use of some basic tools in Vijeo Designer. Please follow the procedure below to build this function yourself.
01) Create a Project named AutoLogoutForSecurity
02) Create a Security Group
03) Create a User
04) Set Target Security to "Use Security"
05) Drag a Login Part on to the Screen
06) Create an INT Variable named "Timer"
07) Create an INT Variable named "AutoLogoutThreshold". Set its initial value to 10 for 10 seconds
08) Draw Numeric Displays for both Variables with labels
09) Create an action with "Trigger Type" set to "Event" and "Trigger Event" set to "When Touch Panel"
10) Set the action's operation to reset "Timer" to 0
11) Create an action with Trigger Type set to "Periodic" and "Frequency" set to 1 second.
12) Set the action's operation to Decision.
13) Set the Condition to (Timer < AutoLogoutThreshold)
14) If the conditon is True, increment "Timer". If the conditon is False, Run the Script "Sys.logout();" and reset "Timer" to 0
This will result in a project that has the ability to change the InActivity timeout to any value from 0 to 63563 seconds.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.