How is the S-Flex wired to use or not use the Smoke Purge feature?
Issue:
Wiring S-Flex for the Smoke Purge feature.
Product Line:
S-Flex
Environment:
S-Flex with Bypass option
Cause:
Wiring to enable or disable smoke purge
Resolution:
All S-Flex Series E units that have the BYPASS option will also have a SMOKE PURGE feature, although it is disabled. To enable the smoke purge function, simply remove the jumper from terminals 3-4 and place it on terminals 9-10. This feature includes a smoke purge relay, SPR, that is activated by applying 120Vac across terminals 17-18. When activated, SPR contacts will disable the AFC / BYP controls and energize the bypass contactor coil. The motor will run with full voltage AC power.
Wiring S-Flex for the Smoke Purge feature.
Product Line:
S-Flex
Environment:
S-Flex with Bypass option
Cause:
Wiring to enable or disable smoke purge
Resolution:
All S-Flex Series E units that have the BYPASS option will also have a SMOKE PURGE feature, although it is disabled. To enable the smoke purge function, simply remove the jumper from terminals 3-4 and place it on terminals 9-10. This feature includes a smoke purge relay, SPR, that is activated by applying 120Vac across terminals 17-18. When activated, SPR contacts will disable the AFC / BYP controls and energize the bypass contactor coil. The motor will run with full voltage AC power.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.