Video: How do I calibrate the Analog Output (FM) on the ATV212 drive?
When using voltage (0-10Vdc) connect your load prior to calibration. When using current (4-20mA) connect the load after calibration.
If you want to follow OUTPUT CURRENT (FMSL = 1)
4-20mA (no load)
4-20mA (no load)
Note: Calibration can also be performed using the VW3A1101 remote keypad. Turn the knob clockwise instead of using the up arrow and turn counter clockwise instead of using the down arrow.
If you want to follow OUTPUT CURRENT (FMSL = 1)
4-20mA (no load)
- Set DIP switch FM (SW101) to "I" (left)
- Set F692 for 20 (20% of 20mA = 4mA)
- Set FMSL to 15
- Go to parameter FM and enter
- Connect the current meter to terminals FM and CC
- Press the UP and DOWN arrows until meter reads desired 100% (20mA)
- Press enter to lock in the scale
- Set FMSL = 1 to follow motor current
- Set DIP switch FM (SW101) to "U" (right)
- Set F692 to 0 (0% of 10V = 0V)
- Set FMSL to 15
- Go to parameter FM and enter
- Connect the volt meter to terminals FM and CC
- Press the UP and DOWN arrows until meter reads desired 100% (10Vdc)
- Press enter to lock in the scale
- Set FMSL = 1 to follow motor current
4-20mA (no load)
- Set DIP switch FM (SW101) to "I" (left)
- Set F692 for 20 (20% of 20mA = 4mA)
- Set FMSL to 17
- Go to the FM parameter and enter
- Connect the current meter to terminals FM and CC
- Press the UP and DOWN arrows until meter reads desired 100% (20mA)
- Press enter to lock in the scale
- Set FMSL back to the analog output function you want to follow per the table below.
1. Set DIP switch FM (SW101) to "U" (right)
2. Set F692 to 0 (0% of 10V = 0V)
3. Set FMSL to 17
4. Go to parameter FM and enter
5. Connect the meter between terminals FM and CC
6. Press the UP and DOWN arrows until meter reads desired 100% (10Vdc)
7. Press enter to lock in the scale
8. Set FMSL back to the analog output function you want to follow, per the table attached.
2. Set F692 to 0 (0% of 10V = 0V)
3. Set FMSL to 17
4. Go to parameter FM and enter
5. Connect the meter between terminals FM and CC
6. Press the UP and DOWN arrows until meter reads desired 100% (10Vdc)
7. Press enter to lock in the scale
8. Set FMSL back to the analog output function you want to follow, per the table attached.
Note: Calibration can also be performed using the VW3A1101 remote keypad. Turn the knob clockwise instead of using the up arrow and turn counter clockwise instead of using the down arrow.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Produkt:
Zjistěte více
Produkt:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.