Can the BME XBP **00 Ethernet backplane be used as an extension rack in the M580 architecture?

Issue:

Can the BME XBP **00 Ethernet backplane be used as an extension rack in the M580 architecture?

Product Line:

BME XBP **00 Ethernet backplane, M580, Control Expert

Resolution:

Yes, you can use this type of backplane as an expansion rack but you will not be able to use
the ethernet based IO modules such as HART and SCAIME. It's for that reason why using the
BMX XBPxx00 would be a better choice.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.