High CPU spike on FrameworkServices

Issue
User is observing very high CPU usage from the FrameworkService

Product Line
Power Monitoring Expert 8.0

Environment
Windows Task Manager

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

1) Download the zip file attached to this article
2) Backup the files listed at the bottom of this email
3) Stop all of the Power Monitoring Expert Services  (They start with ION and ApplicationModules)
4) Replace the dll's with the attached ones in the corresponding locations of the Power Monitoring Expert Installation (Application Server).
5) Restart the services.

The list of files contained in this hotfix include:
...\Power Monitoring Expert\Applications\AlarmConfiguration\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\ApplicationFramework\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\EWS\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\HierarchyManager\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\RateEditor\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\SystemDataService\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\TrendsWebServices\bin\Framework.Common.dll
...\Power monitoring Expert\system\bin\Framework.Common.dll
...\Power monitoring Expert\system\ReportDataService\bin\Framework.Common.dll
...\Power monitoring Expert\Web\bin\Framework.Common.dll

Schneider Electric Česká republika

Přílohy
Hotfix_54857_Dashboards_Hierarchies_FrameworkServicesCPUSpike.zip [2.04 MB]
Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie