How to Configure PowerSCADA Operation to Run as a Service
Issue
Downtime in the event of a system reboot.
Product Line
PowerSCADA Operation (PSE) 8.x
Environment
Runtime
Cause
For applications that provide runtime and historical data to clients, a service interruption cannot be tolerated. The application should start automatically at system power on to minimize downtime.
Resolution
When PSE is installed, the service 'Citect Runtime Manager' is created. This service adds the functionality to start the project automatically after the server is restarted. Follow these two steps to configure this service:
1. Add a dependency to FlexNet Licensing Service. Open a command prompt (DOS window) and type this command to run:
2. Change the startup type to 'Automatic (Delayed Start)' and start the Citect Runtime Manager service.
Now the user can log in and log out without disrupting the system. For complete information refer to System Development Guide for PSE 8.1.
Downtime in the event of a system reboot.
Product Line
PowerSCADA Operation (PSE) 8.x
Environment
Runtime
Cause
For applications that provide runtime and historical data to clients, a service interruption cannot be tolerated. The application should start automatically at system power on to minimize downtime.
Resolution
When PSE is installed, the service 'Citect Runtime Manager' is created. This service adds the functionality to start the project automatically after the server is restarted. Follow these two steps to configure this service:
1. Add a dependency to FlexNet Licensing Service. Open a command prompt (DOS window) and type this command to run:
sc config "Citect Runtime Manager" depend= "FlexNet Licensing Service"
2. Change the startup type to 'Automatic (Delayed Start)' and start the Citect Runtime Manager service.
Now the user can log in and log out without disrupting the system. For complete information refer to System Development Guide for PSE 8.1.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.