How to resolve the error: Integrity Check -Severe Warning on the LMBrick.dlm and LMBrickX.dlm missing or corrupted when launching Unity Pro v11?
Issue:
How to resolve the error:  Integrity Check -Severe Warning on the LMBrick.dlm and LMBrickX.dlm missing or corrupted when launching Unity Pro v11?

Product Line:
Unity Pro

Environment:


Cause:


Resolution:
Close Unity Pro.
Unzip and copy the LMBrick.dlm and LMBrickX.dlm from the attached file to the following path C:\Program Files (x86)\Schneider Electric\Unity Pro\
Once the files are copied, launch Unity to confirm the issue is resolved.

Note:  These files will work for Unity Pro v8 to v11 only.

If the attached files did not resolve the issue.  Please contact Schneider Electric Technical Support.