What are the maximum DNP base points for ION8650 A, B and C Meters?

Issue
ION8650 meters do not allow the configuration of more than 100 DNP base points from ION Setup
It will actually let you keep adding to the parameter map but when you exit setup assistant it throws this message:
"The following modules are off-line and may indicate an improperly configured feature in the device" as shown below:

What are the maximum DNP base points for ION8650 A, B and C Meters

When you try to bring the modules online, the following error message is displayed:
"Too many DNP points configured in DSE" as shown below:

What are the maximum DNP base points for ION8650 A, B and C Meters

What are the maximum DNP base points for ION8650 A, B and C Meters

Product Line
ION 8650 Meters A, B and C
ION Setup

Environment
ION8650 DNP Static Points

Cause
Unable to configure over a 100 DNP base points on an ION8650s in ION Setup

Resolution
The limitation for DNP base points on ION 8650 meters is 100 as stated below:
What are the maximum DNP base points for ION8650 A, B and C Meters
This information can be found under the Powerlogic ION8650 DNP 3.0 Device Profile document, which can be downloaded from the link below

http://download.schneider-electric.com/files?p_Reference=70022-0126-00&p_EnDocType=User guide&p_File_Id=27606449&p_File_Name=70022-0126-00.pdf

Schneider Electric Česká republika

Zjistěte více

Řada:

Zjistěte více

Řada:

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.