Jak vám dnes můžeme pomoci?
How many Modbus RTU server devices can be connected to an HMIGTO
Issue:
Looking for specifications on how many Modbus RTU server devices can be connected to an HMIGTO
Product LIne:
Harmony, Mageils, HMIGTO, HMIGTU, HMISTU, XBTGT, XBTGK, HMIGK
Resolution:
The maximum number of Modbus RTU server devices that can be connected to a Magelis HMIGTO is 32.
The RS-485 communication cable has to be shielded and terminated properly and the maximum distance between devices is 100ft.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.