How many Modbus RTU server devices can be connected to an HMIGTO
Issue:
Looking for specifications on how many Modbus RTU server devices can be connected to an HMIGTO
Product LIne:
Harmony, Mageils, HMIGTO, HMIGTU, HMISTU, XBTGT, XBTGK, HMIGK
Resolution:
The maximum number of Modbus RTU server devices that can be connected to a Magelis HMIGTO is 32.
The RS-485 communication cable has to be shielded and terminated properly and the maximum distance between devices is 100ft.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.