Video: Data Center Expert | How do I control APC Switched Rack PDUs?
Issue:
Process for controlling APC Switched Rack PDU outlets from StruxureWare Data Center Expert.
Product Line:
StruxureWare Data Center Expert (DCE)
- Virtual Appliance (AP94VMACT)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
Environment:
StruxureWare Data Center Expert (all versions)
APC Switched Rack PDUs
Resolution:
1) Log into the DCE client and navigate to the Monitoring perspective and Device View pane.
2) Right-click on the Switched Rack PDU and select Outlet Control.
3) Select the checkboxes for the outlets that you would like to control.
NOTE: When you perform a command at an outlet that is part of an outlet group, that command will be executed at all outlets in the group.
4) Select the command to perform for the selected outlets.
5) Select perform command and the commands will be issued to the outlets that are selected.
Process for controlling APC Switched Rack PDU outlets from StruxureWare Data Center Expert.
Product Line:
StruxureWare Data Center Expert (DCE)
- Virtual Appliance (AP94VMACT)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
Environment:
StruxureWare Data Center Expert (all versions)
APC Switched Rack PDUs
Resolution:
1) Log into the DCE client and navigate to the Monitoring perspective and Device View pane.
2) Right-click on the Switched Rack PDU and select Outlet Control.
3) Select the checkboxes for the outlets that you would like to control.
NOTE: When you perform a command at an outlet that is part of an outlet group, that command will be executed at all outlets in the group.
4) Select the command to perform for the selected outlets.
5) Select perform command and the commands will be issued to the outlets that are selected.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.