What is the maximum permitted distance between the 140ARI03010 and the sensor?

Issue:

What is the maximum permitted distance between the 140ARI03010 and the sensor?

Product Line:

140ARI03010

Resolution:

When using 3 or 4 wire RTD's the maximum distance between the module and the sensor is 200 meters.
If you're using 2 wire RTD's the distance is limited only by the user defined accuracy of the application.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.