How do I set a bit when we press the ACKAll button an Alarm Summary in Vijeo Designer Runtime?

Issue:
How do I set a bit when we press the ACKAll button an Alarm Summary in Vijeo Designer Runtime?

Product Line:
Vijeo Designer (all versions)

Resolution:
To set a bit when pressing the ACKAll button on an alarm summary requires you to draw an invisble switch over the existing ACKAll button.

The invisible switch should have the following operations defined:
1) Alarms & Events --> AckAll on your AlarmSummary
2) Bit -> Set on your BOOLEAN Variable.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.