What is the InFD (Internal Error 13) Fault on the Altivar Process Drive?
Issue:
Getting InFD Fault on the Altivar Process Drive.

Product Line:
Altivar Process Drive System (ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
Drive is displaying an Internal Error 13

Resolution:
An InFD is an Internal Error 13 (Differential Current Deviation Error).
Possible Causes:
  • One or more bricks are not operating
    • List of bricks in the Altivar Drive Systems (ATV660, ATV680, ATV960, ATV980)
      • Rectifier Brick
      • Inverter Brick
      • Filter Brick
      • Active Front End (AFE) Brick
  • Current transformer of the bricks are damaged
    • The current transformer are located on the Inverter Brick.
    • Inverter Brick may have to be replaced.
Remedies:
*Only authorize personnel should perform these task*
  • Check Power Board to Invert Brick cable.
    • Check pin connections
    • Reseat
  • Measure U/V/W phase currents of each brick on the paralleling choke to identify the brick with less output current.
  • Manually test IGBT on each Brick with a multimeter.
    • Open Motor choke connections when performing test.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie